transformer oil gas analyzers 产品详情
model 4003 facilitates the analysis of transformer oil gases in support of astm d3612-02, method a, utilizing a dual-channel flame ionization and thermal conductivity detector (fid/tcd). the purged sampling-valve housing and passivated tubing ensures less sample absorption, while the injection port and gas sampling valve offer flexibility for the introduction of various sample types. a high capacity methanizer for maximum co and co2 conversion is featured on this instrument to ensure productivity and accuracy of each analysis. detection limits on the tcd channel are 1 ppm for h2 and 500 ppm for oxygen and nitrogen, and the fid channel offers a detection limit of 2 for acetylene, and 1ppm for carbon dioxide, carbon monoxide, methane, ethane and ethylene.
规格检测方法astm d3612-01, method a
型号兼容clarus 590 ppc
typemodel 4003
更多