transformers are often one of the most substantial capital assets of an operation. measuring levels of light gases found in an electrical transformer’s insulating oil is an effective way to monitor th......
transformer oil gas analyzers 产品详情
model 4003 facilitates the analysis of transformer oil gases in support of astm d3612-02, method a, utilizing a dual-channel flame ionization and thermal conductivity detector (fid/tcd). the purged sampling-valve housing and passivated tubing ensures less sample absorption, while the injection port and gas sampling valve offer flexibility for the introduction of various sample types. a high capacity methanizer for maximum co and co2 conversion is featured on this instrument to ensure productivity and accuracy of each analysis. detection limits on the tcd channel are 1 ppm for h2 and 500 ppm for oxygen and nitrogen, and the fid channel offers a detection limit of 2 for acetylene, and 1ppm for carbon dioxide, carbon monoxide, methane, ethane and ethylene.
规格检测方法astm d3612-01, method a
型号兼容clarus 590 ppc
typemodel 4003
更多